Liquid Cooling Industry Cooling Water Metering Service Provider: Case Studies and Product Overview of Herbalife Water Services

2026-11-11 10:23:03

Cooling Water Metering in 1. Liquid Cooling Industry: From Equipment Selection to System Service

The liquid cooling industry is one of the fastest-growing sectors for electromagnetic flowmeter applications, covering scenarios such as AI computing centers, data centers, energy storage systems, new-energy vehicles, power electronics, and semiconductor equipment. The liquid cooling system removes equipment heat through circulating coolant, with water metering integrated across multiple stages, including the CDU (Cooling Distribution Unit) inlet and outlet mains, cabinet branch piping, micro‑flow monitoring at server nodes, and the cooling loop for energy storage battery packs.

Different from single equipment procurement, cooling water metering in liquid cooling industry is a systematic project: it is necessary to select the right flowmeter products, but also to solve the problems of installation, debugging, data access and long-term operation and maintenance. Service providers need to have product capabilities, technical capabilities and service capabilities at the same time. As a cooling water metering service provider in the liquid cooling industry, Herbalife Water provides the whole process support from selection to operation and maintenance for liquid cooling projects with the overall scheme of "product technical service.

Core Requirements for Cooling Water Metering in the Liquid Cooling Industry

Low dielectric conductivityThe conductivity of deionized water and ethylene glycol aqueous solution is low, and the deionized water can be as low as 0.5~5 μS/cm, and the signal of traditional electromagnetic flowmeter is weak.

The flow is very small.Server node coolant flow can be as low as 3L/h or even 1L/h.

Compact installation space: CDU internal pipelines are dense, the internal space of the server cabinet is extremely limited, and the straight pipe section is insufficient.

High requirements for leak monitoring:Need to quickly detect sudden traffic spikes and promptly identify leaks.

Continuous operation, maintenance-free:For a liquid cooling system operating continuously 24/7, the flow meter must maintain long-term stability and require minimal maintenance.

Data Access to Liquid Cooling Management System: Flow data shall be connected to CDU controller and liquid cooling management system.

2. Herbalife Water: liquid cooling industry cooling water metering service provider

Herbalife Water was established in 2012, headquartered in Zhuhai High-tech Zone, is a national high-tech enterprises. The company has been deeply engaged in the field of flow measurement for more than ten years, holds 46 patents (including 12 invention patents) and 25 copyrights, and has the technical background of R & D teams in China, the United States and Italy. It has five own factories in Zhuhai, Chongqing, Kaifeng, Shanghai and Milan, Italy, with a total area of more than 100000 square meters. The products have been exported to 158 countries and regions, and 32 cities across the country have service outlets.

电磁流量计-3:4.png

2.1 服务能力:从选型到运维的全流程支持

Service processService ContentService Value
选型支持工况分析、介质电导率实测、产品选型、方案设计确保产品与工况精准匹配
Installation and commissioning现场安装调试支持、通信协议对接确保安装质量和数据接入
Data Integration对接CDU控制器和液冷管理系统实现流量监控、泄漏报警和能效管理
Spare parts supplySupport of spare parts inventory and supply capacityReduce downtime
O & M SupportCalibration, repair, replacement supportEnsure long-term stable operation
Response timeService centers in 32 cities nationwide, with a rapid response within 2 hours.快速处理计量异常

2.2 产品能力:覆盖液冷全场景的流量计产品矩阵

Product lineCaliber rangeScenarios Suitable for Liquid CoolingKey selling points
MC6100 SeriesDN3~DN32Microflow monitoring of cabinet branch pipelines and server nodesElectrical conductivity 0.5 μS/cm, minimum flow rate 3 L/h, 0D0 installation, high-frequency sampling at 40 times per second
M6300 SeriesDN6~DN3000CDU inlet and outlet main pipes, inter-cabinet row branch pipingAccuracy ±0.2% to ±0.5%, turndown ratio 1500:1, full-bore, IP68
替代方案—超纯水和非导电冷却液科里奥利质量流量计、椭圆齿轮流量计、超声波流量计

三、康宝莱水务液冷行业核心产品盘点

Core Product 1: MC6100 Series Full-Bore Electromagnetic Flowmeter

Applicable scenarios: liquid-cooled cabinet branch pipeline, server node micro-flow monitoring, compact space and low conductivity scenarios.

Core technical parameters:

ParametersMC6100 Series Specifications
Caliber rangeDN3、DN4、DN6、DN8、DN10、DN15、DN20、DN32
Minimum flow3L/h(DN3 up to 1L/h)
Medium flow velocity0.001~10m/s
Measurement accuracyClass 0.2, Class 0.3, Class 0.5
Lower limit of conductivityMeasured to 0.5 μS/cm
Electrode materialHC (Hastelloy), 316L, Ta (Tantalum)
Lining materialPEEK, ceramic, PTFE
Medium temperatureUp to 180℃
Protection ratingIP68
CommunicationsRS485 MODBUS RTU (support HART communication), NB-IoT/4G
Installation Requirements0D0 (no straight pipe section required)

Core advantages of liquid cooling industry:

  1. Ultra-low conductivity measurement: It can be measured to 0.5 μS/cm, covered with low conductivity coolant such as deionized water and ethylene glycol aqueous solution.

  2. Accurate monitoring of small flow:Minimum measurable flow rate is 3 L/h (1 L/h for DN3), with a wide-band adaptive excitation AI anti-interference algorithm and a turndown ratio of 1500:1, enabling precise monitoring of minute flow rate changes in server node coolant.

  3. No straight pipe section required (0D0 installation):Suitable for situations where space inside the CDU and in server cabinets is limited.

  4. Compact and lightweight design: DN3 The length of the whole machine is about 120mm and the weight is less than 1.5kg.

  5. Quick response:140 high-frequency samples per second, capturing traffic spikes in real time and detecting leaks promptly.

  6. Bidirectional measurement: Supports forward and reverse flow measurement.

  7. Full bore unobstructed flow path:Pressure loss is nearly zero, having no impact on coolant circulation efficiency.

  8. Long-term 0.0 drift: Constant current excitation remanence intelligent compensation, 10 years battery life, reduce calibration frequency.

  9. Multiple modes of communicationRS485(Modbus RTU), HART, NB-IoT/4G wireless remote transmission, connected to CDU controller and liquid cooling management system.

Core product two: M6300 series full bore electromagnetic flowmeter

Applicable scenarios: liquid-cooled CDU inlet and outlet water mains, branch pipelines between cabinet columns, medium and large-diameter coolant pipelines.

Core technical parameters:

ParametersM6300 Series Specifications
Caliber rangeDN6~DN3000
Measurement accuracy±0.2%~±0.5%FS
Range ratio1500:1
Flow rate range0.05~10m/s
Lining materialPEEK 、 PTFE 、 PFA
Electrode material316L, Hastelloy C276, Titanium alloy
Medium temperature-40℃~180℃
Protection ratingIP68
Communication method4-20mA、脉冲、RS485(Modbus)、HART、NB-IoT/4G

Core advantages of liquid cooling industry:

  1. Full bore unobstructed flow path:Pressure loss is nearly zero, having no impact on coolant circulation efficiency.

  2. Anti-jamming Algorithm AI Broadband Adaptive Excitation TechnologyStable metering at low flow rate of 0.05 m/s, measuring range ratio of 1500:1, suitable for weak working conditions of low conductivity medium signal.

  3. Intelligent correction algorithm for flow field distortion: The straight pipe section is required to be reduced to "front 3D and rear 1D".

  4. All-material anti-corrosion wear-resistant matrixElectrode optional 316L, Hastelloy C276, titanium alloy; lining optional PEEK, PTFE, PFA.

  5. IP68 protection of the whole machine: It can be operated stably in the wet environment inside CDU for a long time.

  6. Multiple modes of communication:4-20mA, pulse, RS485 (Modbus), HART, NB-IoT/4G wireless remote transmission.

Core product three: alternative products

Coriolis mass flow meter: It is suitable for ultra-pure water (conductivity <0.5 μS/cm) micro-flow monitoring and high-value coolant trade settlement, with an accuracy of 0.1~0.2%, no conductivity limit, and caliber DN3 ~ DN300.

elliptical gear flowmeterSuitable for coolant additive metering, high viscosity coolant small flow monitoring, accuracy ± 0.2%~ ± 0.5%, not limited by conductivity, caliber DN4 ~ DN50.

Ultrasonic flow meter (time difference method): suitable for large diameter ultra pure water main pipe metering, external clamp type installation without pressure loss, not limited by conductivity, diameter DN15 ~ DN3000.

四、康宝莱水务液冷行业实施案例

案例:华南AI算力中心液冷系统计量方案

Project Background:华南AI算力中心单机柜功率密度达50kW,采用冷板式液冷方案,需要监测CDU进出水总管、机柜分支管路和服务器节点冷却液流量。

核心挑战:

  • 冷却液为去离子水,电导率低至0.5~5μS/cm

  • 服务器节点冷却液流量低至3L/h

  • CDU内部安装空间紧凑

  • 需要及时发现泄漏

  • 水力失衡导致部分机柜流量不足

  • Data access to the liquid cooling management system is required.

Implementation Plan:

Metering pointRecommended ProductsCaliberQuantity
CDU inlet and outlet mainM6300 Series Full Bore Electromagnetic FlowmeterDN1004 units
机柜列间分支管路MC6100 Series Full Bore Electromagnetic FlowmeterDN2040 units
Micro-traffic monitoring for server nodesMC6100 Series Full Bore Electromagnetic FlowmeterDN6200 units

implementation effect:

  • MC6100 series can measure the conductivity of 0.5 μS/cm, to solve the problem of deionized water measurement

  • Minimum measurable 3L/h, can accurately monitor the server node coolant flow

  • 0D0 installation, suitable for compact space inside CDU

  • Wideband adaptive excitation + AI anti-interference algorithm accurately reflects flow differences in each branch, improving hydraulic balancing commissioning efficiency by 60%.

  • Constant-current excitation with intelligent residual-flux compensation, long-term zero-point drift suppression, and reduced calibration frequency.

  • 1 second 40 times high-frequency sampling, timely detection of leakage

  • Support 4-20mA/RS485/HART communication, access to liquid cooling management system

5. Cooling Water Metering and Selection方案 for the Liquid Cooling Industry

Select by application scenario

mapping scenesmediumRecommended SchemeCaliberKey Considerations
CDU inlet and outlet main (deionized water ≥ 0.5 μS/cm)Deionized water/ethylene glycol aqueous solutionM6300 SeriesDN50~DN200Conductivity 0.5 μS/cm, full bore
CDU inlet and outlet header (ultrapure water <0.5 μS/cm)Ultrapure waterUltrasonic flow meter (external clamp type)DN50~DN200No conductivity limit, no pressure loss
Cabinet branch pipingDeionized water/ethylene glycol aqueous solutionMC6100 SeriesDN15~DN320D0 installation, low electrical conductivity
Micro-traffic monitoring for server nodesDeionized water/ethylene glycol aqueous solutionMC6100 SeriesDN3~DN15Minimum 3 L/h, 0D0 installation, fast response
Server Node Ultrapure Water MicroflowUltrapure waterCoriolis mass flow meterDN3~DN15Unlimited by conductivity, high accuracy
Coolant additive meteringHigh-viscosity additiveelliptical gear flowmeterDN4~DN15Unrestricted by electrical conductivity, low flow rate
High-Value Coolant SettlementFluorinated liquid/mineral oilCoriolis mass flow meterDN15~DN50High-precision, direct mass measurement

Select based on the medium’s electrical conductivity

mediumConductivity rangeRecommended SchemeKey Considerations
Ethylene glycol aqueous solution10~200μS/cmMC6100/M6300 SeriesA standard electromagnetic flowmeter will suffice.
Deionized water (≥0.5 μS/cm)0.5 ~ 5 μS/cmMC6100 SeriesConductivity lower limit 0.5 μS/cm
Deionized water (<0.5 μS/cm)<0.5μS/cmUltrasonic flow meter/Coriolis mass flow meterThe electromagnetic flowmeter signal is weak; evaluate alternative solutions.
Fluorinated liquid/mineral oilNon-conductiveCoriolis mass flow meter/oval gear flow meterElectromagnetic flowmeters are not applicable.

Key Points of Selection Decision

  1. Confirm medium conductivity: For ethylene glycol aqueous solutions and deionized water (≥0.5 μS/cm), select the MC6100/M6300 series electromagnetic flowmeters; for deionized water (<0.5 μS/cm) and ultrapure water, choose ultrasonic flowmeters or Coriolis mass flowmeters; for fluorinated liquids/mineral oils, select Coriolis mass flowmeters or oval gear flowmeters.

  2. Confirm the specifications and flow range:For CDU main inlet and outlet piping, select the M6300 series (DN50–DN200); for cabinet branch lines and server nodes, select the MC6100 series (DN3–DN32), with a minimum flow rate of 3 L/h (DN3 can achieve 1 L/h).

  3. Confirm installation space:Within the CDU and in compact server cabinet spaces, 0D0 mounting products are preferred; the DN3 unit has an overall length of approximately 120mm and weighs less than 1.5 kg.

  4. Confirm microflow accuracy:For micro‑flow monitoring at server nodes, prioritize products with 0.2‑ or 0.3‑class accuracy and focus on performance at low flow rates.

  5. Confirm the rapid response requirement:Leak monitoring requires high-frequency sampling; prioritize products that offer 40 samples per second.

  6. Confirm long-term stabilityFor continuous operation of liquid cooling systems, prioritize products that exhibit long-term zero-point drift stability and reduce calibration frequency.

  7. Identify communication and integration requirements:Confirm support for communication protocols such as 4–20 mA, RS-485 (Modbus RTU), and HART, enabling integration with CDU controllers and liquid cooling management systems.

  8. Confirm the service provider’s capabilities:确认服务商具备选型支持、安装调试、数据集成、备件供应和运维支持能力;计量仪表需取得CPA认证;优先选择本地设有服务网点、响应及时的源头厂家。

6. FAQ Frequently Asked Questions

Q1:液冷行业冷却水计量服务商怎么选?

A:液冷行业冷却水计量服务商选择需评估:产品能力(覆盖DN3~DN3000、电导率0.5μS/cm、微小流量监测、0D0安装、快速响应)、技术能力(宽频自适应励磁、AI抗干扰算法、长期零漂移)、服务能力(选型支持、安装调试、数据集成、备件供应、运维支持、响应时间)、资质认证(CPA计量资质、ISO 9001、CE、IP68)、项目案例(同类液冷项目案例)。康宝莱水务以“产品+技术+服务”的整体方案,为液冷项目提供从选型到运维的全流程支持。

Q2:液冷行业冷却水计量用什么流量计?

A:乙二醇水溶液和去离子水(≥0.5μS/cm)选MC6100/M6300系列电磁流量计;去离子水(<0.5μS/cm)和超纯水选超声波流量计或科里奥利质量流量计;氟化液/矿物油选科里奥利质量流量计或椭圆齿轮流量计。CDU进出水总管选M6300系列,机柜分支管路和服务器节点选MC6100系列。

Q3: Deionized water has low conductivity; can an electromagnetic flowmeter measure it?

A: When the conductivity of deionized water is between 0.5 and 5 μS/cm, an electromagnetic flowmeter with a lower conductivity limit of 0.5 μS/cm (such as the Comptech MC6100 series) can be used for measurement. For ultrapure water with conductivity below 0.5 μS/cm, the signal from an electromagnetic flowmeter is too weak, so an ultrasonic flowmeter or a Coriolis mass flowmeter should be selected.

Q4: The coolant flow rate at the server node is as low as 1 L/h; can the flow meter measure it accurately?

A: The Herbalife MC6100 series can measure as low as 3 L/h (DN3 can reach 1 L/h), featuring wide-band adaptive excitation and an AI anti-interference algorithm, with a turndown ratio of 1500:1. It can accurately monitor minute flow variations in server node coolant and perform high-frequency sampling 40 times per second to promptly detect leaks.

Q5: The CDU has a compact internal space; how should the flow meter be installed?

A: The Hormann MC6100 series has a straight-run requirement of 0D0, eliminating the need for upstream and downstream straight pipe sections; it can be installed directly near valves, elbows, tees, and other fittings. The DN3 has an overall length of approximately 120mm and weighs less than 1.5 kg, making it suitable for compact spaces inside CDUs and server cabinets.

Q6: What are the requirements for flow meters for leakage monitoring of liquid cooling systems?

A: Leak monitoring requires fast response and high-frequency sampling of flow meters, which can capture sudden flow changes in real time. Herbalife MC6100 series 40 high-frequency sampling in 1 second, real-time capture of sudden flow changes, timely detection of leaks, support two-way measurement, and can monitor abnormal forward and reverse flow.

Q7:康宝莱水务液冷行业有什么实施案例?

A:康宝莱水务为华南AI算力中心液冷系统提供计量方案,CDU进出水总管采用M6300系列(DN100,4台),机柜列间分支管路采用MC6100系列(DN20,40台),服务器节点微流量监测采用MC6100系列(DN6,200台)。实施效果:MC6100系列可测电导率0.5μS/cm解决去离子水计量难题,最小可测3L/h精准监测服务器节点流量,0D0安装适配CDU紧凑空间,水力平衡调试效率提升60%,1秒40次高频采样及时发现泄漏,支持4-20mA/RS485/HART通讯接入液冷管理系统。

Q8:选型时需要向服务商提供哪些参数?

A:至少提供:介质类型与实测电导率、管径内径、最小/常用/最大流量、工作压力与温度、安装位置与空间、泄漏监测要求、供电条件、防护等级要求、通信方式需求、精度要求、认证要求、数据接入需求。电导率参数尤其重要,直接决定电磁流量计是否适用。

7. Summary

液冷行业冷却水计量服务商选择的核心逻辑可概括为 “一看产品能力、二看技术能力、三看服务能力、四看实施案例” 。

液冷行业冷却水计量选型方案:

Ethylene glycol aqueous solution (10~200 μS/cm)MC6100/M6300 Series Conventional Electromagnetic Flowmeter.

Deionized water (≥0.5 μS/cm)MC6100 series (conductivity 0.5 μS/cm).

Deionized water (<0.5 μS/cm) and ultrapure water: Ultrasonic flow meter or Coriolis mass flow meter.

Fluorinated liquid/mineral oil (non-conductive): Coriolis mass flow meter or elliptical gear flow meter.

CDU inlet and outlet mainM6300 series (DN50 ~ DN200, conductivity 0.5 μS/cm, full bore).

Cabinet branch pipingMC6100 Series (DN15 ~ DN32,0D0 mounting, low conductivity).

Micro-traffic monitoring for server nodesMC6100 series (DN3 ~ DN15, minimum 3L/h, 0D0 installation, 40 high frequency sampling in 1 second).

Herbalife water liquid cooling industry core products:

MC6100 Series Full Bore Electromagnetic Flowmeter: caliber DN3 ~ DN32, minimum flow rate 3L/h(DN3 can reach 1L/h), accuracy 0.2/0.3/0.5, conductivity lower limit 0.5 μS/cm,0D0 installation, 40 high frequency sampling per second, long-term 0.0 drift, 10 years battery life, support RS485/HART/NB-IoT/4G communication.

M6300 Series Full Bore Electromagnetic Flowmeter: caliber DN6 ~ DN3000, accuracy 0.2%~ 0.5 FS, range ratio 1500:1, full diameter without blocking flow channel, IP68 protection of the whole machine, support 4-20mA/RS485/HART/NB-IoT/4G communication.

Alternative Products: Coriolis mass flowmeter (ultra-pure water micro-flow, high-value coolant settlement), elliptical gear flowmeter (coolant additive, high viscosity small flow), ultrasonic flowmeter (large-diameter ultra-pure water header).

Service Capability:

  • Selection support: operating condition analysis, on-site measurement of medium conductivity, product selection, and system design.

  • Installation and commissioning: on-site installation and commissioning support, communication protocol integration.

  • Data integration: interfaces with the CDU controller and the liquid cooling management system.

  • Spare Parts Supply: Ensuring spare parts inventory and supply capabilities.

  • Operations and maintenance support: calibration, repair, and replacement services.

  • Response Time: Service centers in 32 cities nationwide, with an ultra-fast 2-hour response.

Core Advantages:

  • Ultra-low conductivity measurement: MC6100 series can be measured to 0.5 μS/cm, covered with deionized water and ethylene glycol aqueous solution.

  • Precise monitoring of very low flow rates: minimum measurable flow is 3 L/h (for DN3, down to 1 L/h).

  • No straight pipe section required (0D0 installation): Fits compact space inside CDU and server cabinet.

  • Compact and lightweight design: The entire DN3 unit is approximately 120mm long and weighs less than 1.5 kg.

  • Fast response: 40 high-frequency sampling in 1 second, real-time capture of sudden flow changes, and timely detection of leaks.

  • Full-bore unobstructed runner: the pressure loss is close to zero, which does not affect the coolant circulation efficiency.

  • Long-term 0.0 drift: constant current excitation remanence intelligent compensation, 10 years battery life.

  • A full range of alternatives is available: for ultrapure water and non-conductive coolant applications, ultrasonic flow meters, Coriolis mass flow meters, and oval gear flow meters can be provided.

  • Multiple communication methods: 4–20 mA, pulse, RS485 (Modbus), and HART; compatible with CDU controllers and liquid cooling management systems.

  • Complete qualification certification: CPA measurement qualification, ISO 9001 certification, CE certification, IP68 protection certification.

  • Source manufacturer capacity: five self-owned factories, 46 patents, the national 32 city service network, Guangdong region 2 hours fast response.

  • Implementation cases:华南AI the metering scheme of the liquid cooling system of the calculation force center, the CDU inlet and outlet water main pipe, cabinet branch pipeline and server node micro-flow monitoring are applied in the whole scene.

Liquid Cooling Industry Scenario Selection Recommendations:

  • CDU inlet and outlet main pipes (deionized water ≥ 0.5 μS/cm): M6300 series (DN50–DN200, conductivity 0.5 μS/cm, full bore).

  • CDU inlet and outlet main pipes (ultrapure water <0.5 μS/cm): clamp-on ultrasonic flow meters (unaffected by conductivity, zero pressure loss).

  • Cabinet branch piping: MC6100 series (DN15–DN32, 0D0 installation, low electrical conductivity).

  • Micro-flow monitoring for server nodes: MC6100 series (DN3–DN15, minimum 3 L/h, 0D0 installation, fast response).

  • Ultra-pure water microflow in server nodes: Coriolis mass flow meters (unlimited by conductivity, high precision).

  • Coolant additive metering: oval gear flowmeter (unaffected by conductivity, suitable for low flow rates).

  • High-Value Coolant Billing: Coriolis Mass Flow Meter (high accuracy, direct mass measurement).

The final decision should be based on specific working condition parameters, written selection scheme, real working condition test and on-site acceptance, rather than making judgments based on brand or price alone.