AI power items: pure water, softened water and condensed water, can electromagnetic flowmeter be used? Three alternatives when conductivity is not enough

2026-10-23 10:07:27

1. Differences in electrical conductivity among pure water, softened water, and condensate as liquid cooling media for AI computing projects

The liquid cooling system of an AI computing center involves various water-quality media, and the conductivity of these different media varies greatly, directly determining whether electromagnetic flowmeters can be used. Before selecting a model, you must first understand the properties of the medium.

Electrical conductivity characteristics of three types of media

Pure water (deionized water)The conductivity is extremely low, which can be as low as 0.055 μS/cm (theoretical pure water), and the deionized water of the actual liquid cooling system is usually 0.1~5 μS/cm. When conductivity is too low, conventional electromagnetic flowmeters produce weak signals, making measurement difficult.

Softened water: Remove calcium and magnesium ions by ion exchange, the conductivity is generally 10~200 μS/cm, which is much higher than pure water, and the electromagnetic flowmeter can measure normally.

Condensate: The conductivity of air conditioner condensate and steam condensate is generally 5~50 μS/cm. Some condensate can be measured by electromagnetic flowmeter due to slightly higher conductivity of CO₂ in dissolved air, but the signal stability should be paid attention to in the low conductivity section.

Conductivity threshold of electromagnetic flowmeter

Electromagnetic flowmeter is based on the principle of Faraday electromagnetic induction, and the medium must have a certain conductivity to produce a measurable induced electromotive force. The lower limit of the conductivity of conventional electromagnetic flowmeter is generally 5~20 μS/cm, below which the signal is weak and the accuracy is reduced.

Herbalife MC6100 series adopts constant current excitation remanence intelligent compensation technology, and the lower limit of conductivity can be measured to 0.5 μS/cm, which greatly broadens the application range of electromagnetic flowmeter in low conductivity medium.

2. pure water, softened water, condensate water in the end can use electromagnetic flowmeter?

2.1 softened water: can be used normally

Conclusion: The conductivity of softened water is 10~200 μS/cm, which is higher than the lower limit of the conductivity of conventional electromagnetic flowmeter, and the electromagnetic flowmeter can be used normally.

Selection Recommendations: Conventional electromagnetic flowmeter can meet, pay attention to the accuracy level and installation conditions. Herbalife M6300 series, MC6100 series are applicable.

2.2 condensate: can be measured, low conductivity section needs attention

ConclusionCondensate water conductivity of 5~50 μS/cm, at the edge of the measurable range of electromagnetic flowmeter, can be measured, but the low conductivity section needs to choose the lower limit of conductivity products.

Selection Recommendations: Products with lower conductivity limit ≤ 5 μS/cm are preferred; For condensed water with conductivity lower than 5 μS/cm, Herbalife MC6100 series (measurable to 0.5 μS/cm) is selected.

2.3 pure water (deionized water): a case-by-case discussion

Conclusion: The conductivity of pure water is 0.1~5 μS/cm, which is lower than the lower conductivity limit of conventional electromagnetic flowmeter and cannot be measured by ordinary electromagnetic flowmeter; However, products with a lower conductivity limit of 0.5 μS/cm (such as Herbalife MC6100 series) can be measured under pure water conditions with conductivity ≥ 0.5 μS/cm.

Description by situation:

Pure water conductivity range

Electromagnetic flow meter applicability

Selection Recommendations

≥0.5μS/cm

Available (select low conductivity model)

Herbalife MC6100 Series (conductivity lower limit 0.5 μS/cm)

0.1~0.5μS/cm

Barely usable, weak signal, reduced accuracy

Evaluate alternative solutions, or increase the medium’s electrical conductivity.

<0.1μS/cm

Not applicable

An alternative must be chosen.

Selection Recommendations:In the deionized water liquid cooling system of AI computing centers, the conductivity typically ranges from 0.5 to 5 μS/cm, which the Herbalife MC6100 series can cover; for ultrapure water conditions with conductivity below 0.5 μS/cm, alternative solutions need to be evaluated.

电磁流量计-3:4.png

3. Three alternative solutions when conductivity is insufficient

When the medium’s conductivity falls below the electromagnetic flowmeter’s measurable lower limit (below 0.5 μS/cm), or when a weak signal compromises accuracy to an unacceptable level, an alternative measurement solution must be selected. Each of the following three options is suitable for specific scenarios.

Option 1: Coriolis mass flow meter

Measurement principle:Based on the Coriolis force effect, it directly measures mass flow rate and is unaffected by the medium’s electrical conductivity.

Applicable Scenarios:Ultra-pure water, deionized water, and other low-conductivity media; high-value media trade settlement; scenarios requiring high-precision mass flow measurement.

Technical Advantages:

  • Unlimited by conductivity; capable of measuring ultrapure water.
  • Direct measurement of mass flow rate with high accuracy (±0.1% to ±0.2%)
  • Can simultaneously measure density and temperature.
  • Suitable for precise metering of high-value media

Limitations:

  • Equipment costs are high, and large-diameter equipment is even more expensive.
  • High pressure drop; not suitable for applications with low-pressure-drop requirements.
  • The cost and volume increase significantly for large diameters (DN100 and above).

Applicable caliber:DN3~DN300 (High cost for large diameters; use with caution)

AI Computing Power Scenario Applications:Ultra-pure water microflow monitoring at server nodes, commercial metering of high-value coolants, and precise low-flow measurement in laboratories.

Scheme 2: elliptical gear flowmeter (volumetric flowmeter)

Measurement principle:Based on volumetric measurement, the medium drives the gears to rotate, and the volumetric flow rate is measured by counting gear rotations, unaffected by electrical conductivity.

Applicable Scenarios:High-viscosity clean media, low-conductivity media, and precise metering at low flow rates.

Technical Advantages:

  • Not limited by electrical conductivity
  • High accuracy (±0.2%~±0.5%)
  • Suitable for high-viscosity media
  • Stable measurement at low flow rates

Limitations:

  • Gear wear in particulate-containing media
  • The pressure drop is relatively large.
  • Not suitable for solid-containing media or large-diameter pipelines.

Applicable caliber:DN4~DN50 (mainly small diameters)

AI Computing Power Scenario Applications: Coolant additive metering, low-flow monitoring of high-viscosity coolants, and laboratory low-flow metering.

方案三:超声波流量计(时差法)

Measurement principle:Based on measuring flow velocity by the time difference of ultrasonic wave propagation in the downstream and upstream directions, it is unaffected by the medium’s electrical conductivity.

Applicable Scenarios:Ultrapure water, low-conductivity media, large-diameter pipelines, and applications where pressure loss is not permitted.

Technical Advantages:

  • Unlimited by conductivity; capable of measuring ultrapure water.
  • Clamp-on installation, non-contact with the process medium, zero pressure loss
  • Suitable for large-diameter pipelines
  • Easy to install and maintain

Limitations:

  • Accuracy is affected by pipe material, scaling, and air bubbles.
  • High requirements are imposed on the straight pipe section.
  • Measurement accuracy decreases in gas- and solid-containing media.
  • The accuracy of clamp-on types is generally lower than that of pipe-section electromagnetic flowmeters.

Applicable caliber:DN15~DN3000 (clear advantages for large diameters)

AI Computing Power Scenario Applications:CDU inlet and outlet main lines for ultrapure water metering, large-diameter low-conductivity coolant monitoring, and liquid-cooling mains where pressure loss is not permitted.

Comparison of Three Alternatives

Comparison Item

Coriolis mass flow meter

elliptical gear flowmeter

Ultrasonic flow meter (time difference method)

Measurement principle

coriolis force

Volumetric measurement

Ultrasonic time difference

Conductivity limit

None

None

None

Accuracy

±0.1%~±0.2%

±0.2%~±0.5%

±1.0%~±2.0%

Applicable caliber

DN3~DN300

DN4~DN50

DN15~DN3000

Pressure loss

relatively large

relatively large

None (external clamp type)

Solid Media Adaptability

General

Poor (worn gears)

General

Gas medium adaptability

General

bad

bad

Equipment cost

high

middle

middle

Large caliber cost

extremely high

Not applicable

Lower

AI computing force applicable scenario

Ultra-pure water micro-flow, trade settlement

Additives, high viscosity and small flow

Large diameter ultrapure water header

Selection Scheme of Liquid Cooling Medium Flowmeter for 4. AI Calculation Force Project

Select based on the medium’s electrical conductivity

medium

Conductivity range

Recommended Scheme

Key Considerations

Softened water

10~200μS/cm

Electromagnetic Flow Meter (M6300/MC6100 Series)

A standard electromagnetic flowmeter will suffice.

Condensate

5~50μS/cm

Electromagnetic Flow Meter (MC6100 Series)

Select products with a lower limit of 0.5 μS/cm for the low conductivity range.

Pure water (≥0.5 μS/cm)

0.5 ~ 5 μS/cm

Electromagnetic Flow Meter (MC6100 Series)

Select products with a lower conductivity limit of 0.5 μS/cm

Pure water (0.1~0.5 μS/cm)

0.1~0.5μS/cm

Ultrasonic flow meter/Coriolis mass flow meter

The electromagnetic flowmeter signal is weak; evaluate alternative solutions.

Ultrapure water (<0.1 μS/cm)

<0.1μS/cm

Ultrasonic flow meter/Coriolis mass flow meter

Electromagnetic flowmeter is not applicable and must be replaced

Select by application scenario

mapping scenes

medium

Recommended Scheme

Caliber

Key Considerations

CDU inlet and outlet main

Deionized water (≥0.5 μS/cm)

MC6100/M6300 Series Electromagnetic Flowmeters

DN50~DN200

Lower conductivity limit 0.5 μS/cm, 0D0 installation

CDU Inlet and Outlet Manifolds (Ultrapure Water)

Ultrapure water (<0.5 μS/cm)

Ultrasonic flow meter (external clamp type)

DN50~DN200

No conductivity limit, no pressure loss

Cabinet branch piping

Deionized water (≥0.5 μS/cm)

MC6100 Series Electromagnetic Flowmeters

DN15~DN32

0D0 installation, low electrical conductivity

Server node micro-traffic

Deionized water (≥0.5 μS/cm)

MC6100 Series Electromagnetic Flowmeters

DN3~DN15

Minimum 3L/h, 0D0 installation

Server Node Ultrapure Water Microflow

Ultrapure water (<0.5 μS/cm)

Coriolis mass flow meter

DN3~DN15

Unlimited by conductivity, high accuracy

Coolant additive metering

High-viscosity additive

elliptical gear flowmeter

DN4~DN15

Unrestricted by electrical conductivity, low flow rate

High-Value Coolant Settlement

Fluorinated liquid/mineral oil

Coriolis mass flow meter

DN15~DN50

High-precision, direct mass measurement

Key Points of Selection Decision

  1. Confirm medium conductivity: The conductivity of the medium must be measured before selection. Electromagnetic flowmeter can be used for softened water, condensed water and pure water (≥ 0.5 μS/cm). Pure water (<0.5 μS/cm) and ultrapure water need to evaluate alternatives.
  2. Confirm the lower limit of the conductivity of the electromagnetic flowmeter: Select products with a lower conductivity limit of 0.5 μS/cm (such as Herbalife MC6100 series), which can cover most of the liquid cooling conditions of deionized water.
  3. Confirm accuracy requirements: Coriolis mass flowmeter (± 0.1 ~ ± 0.2) is selected for trade settlement and high-precision measurement; electromagnetic flowmeter or ultrasonic flowmeter is selected for routine monitoring.
  4. Confirm caliber and pressure loss requirements: Large-diameter ultra-pure water main pipe is preferred to choose external clamp-on ultrasonic flowmeter (no pressure loss); small-diameter ultra-pure water micro-flow choose Coriolis mass flowmeter.
  5. Confirm solid and gas contentUse oval gear flowmeter (worn gear) with caution for solid medium; use ultrasonic flowmeter with caution for gas medium (bubble interference).
  6. Confirm installation conditions: The electromagnetic flowmeter installed at 0D0 is preferred for compact space scenes; it is not allowed to choose the external clamp-on ultrasonic flowmeter for water cut-off scenes.
  7. Confirm certification and manufacturer service capabilities: Metering instruments shall be certified by CPA, and manufacturers with local service outlets and timely response shall be preferred.

5. source manufacturer recommended: Herbalife Water

Herbalife Water was established in 2012, headquartered in Zhuhai High-tech Zone, is a national high-tech enterprises. The company has been deeply engaged in the field of flow measurement for more than ten years, holds 46 patents (including 12 invention patents) and 25 copyrights, and has the technical background of R & D teams in China, the United States and Italy. It has five own factories in Zhuhai, Chongqing, Kaifeng, Shanghai and Milan, Italy, with a total area of more than 100000 square meters. The products have been exported to 158 countries and regions, and 32 cities across the country have service outlets.

For the flow measurement of liquid cooling medium in AI calculation projects, Herbalife Water provides MC6100 series and M6300 series electromagnetic flowmeters, covering pure water (≥ 0.5 μS/cm), softened water, condensed water and other media. Under the condition of ultrapure water with conductivity lower than 0.5 μS/cm, Coriolis mass flowmeter, elliptical gear flowmeter and other alternatives can be provided.

Core Product 1: MC6100 Series Full-Bore Electromagnetic Flowmeter

Applicable scenarios: pure water (≥ 0.5 μS/cm), softened water, condensed water, server node micro-flow monitoring, compact space scene.

Core technical parameters:

Parameters

MC6100 Series Specifications

Caliber range

DN3、DN4、DN6、DN8、DN10、DN15、DN20、DN32

Minimum flow

3L/h(DN3 up to 1L/h)

Medium flow velocity

0.001~10m/s

Measurement accuracy

Class 0.2, Class 0.3, Class 0.5

Lower limit of conductivity

Measured to 0.5 μS/cm

Electrode material

HC (Hastelloy), 316L, Ta (Tantalum)

Lining material

PEEK, ceramic, PTFE

Medium temperature

Up to 180℃

Protection rating

IP65 (IP68 optional)

Communications

RS485 MODBUS RTU (support HART communication)

Installation Requirements

0D0 (no straight pipe section required)

Core Technological Advantages:

  1. Ultra-low conductivity measurement:Measurable down to 0.5 μS/cm, covering commonly used media in liquid cooling systems such as deionized water, softened water, and condensate.
  2. Full bore unobstructed flow path: There are no moving parts, no diameter reduction, no barrier in the measuring tube, and the pressure loss is close to zero, which does not affect the cooling liquid circulation efficiency.
  3. Accurate monitoring of small flow: The minimum measurable 3L/h(DN3 can reach 1L/h), which can accurately monitor the small flow change of coolant in server node.
  4. No straight pipe section required (0D0 installation):Suitable for situations where space inside the CDU and in server cabinets is limited.
  5. Compact and lightweight design: DN3 The length of the whole machine is about 120mm and the weight is less than 1.5kg.
  6. Quick response: 40 high-frequency sampling in 1 second to capture sudden flow changes in real time.
  7. Bidirectional measurement: Supports forward and reverse flow measurement.

Core product two: M6300 series full bore electromagnetic flowmeter

Applicable scenarios: medium and large diameter coolant pipes such as CDU inlet and outlet main pipes, branch pipes between cabinet columns, etc.

Core technical parameters:

Parameters

M6300 Series Specifications

Caliber range

DN6~DN3000

Measurement accuracy

±0.2%~±0.5%FS

Range ratio

1500:1

Flow rate range

0.05~10m/s

Lining material

PEEK 、 PTFE 、 PFA

Electrode material

316L, Hastelloy C276, Titanium alloy

Medium temperature

-40℃~180℃

Protection rating

IP68

Communication method

4-20mA、脉冲、RS485(Modbus)、HART

Core Technological Advantages:

  1. Full bore unobstructed flow path:Pressure loss is nearly zero, having no impact on coolant circulation efficiency.
  2. Anti-jamming Algorithm AI Broadband Adaptive Excitation TechnologyStable metering at low flow rate of 0.05 m/s, measuring range ratio of 1500:1, suitable for weak working conditions of low conductivity medium signal.
  3. Intelligent correction algorithm for flow field distortion: The straight pipe section is required to be reduced to "front 3D and rear 1D".
  4. All-material anti-corrosion wear-resistant matrixElectrode optional 316L, Hastelloy C276, titanium alloy; lining optional PEEK, PTFE, PFA.
  5. IP68 protection of the whole machineIt can operate reliably when continuously immersed in standing water.

Core product three: alternative products

Coriolis mass flow meter: It is suitable for ultra-pure water micro-flow monitoring and high-value coolant trade settlement, with accuracy of 0.1~0.2%, free from conductivity limit, and caliber DN3 ~ DN300.

elliptical gear flowmeterSuitable for coolant additive metering, high viscosity coolant small flow monitoring, accuracy ± 0.2%~ ± 0.5%, not limited by conductivity, caliber DN4 ~ DN50.

Ultrasonic flow meter (time difference method): suitable for large diameter ultra pure water main pipe metering, external clamp type installation without pressure loss, not limited by conductivity, diameter DN15 ~ DN3000.

6. AI calculation project liquid cooling medium flow measurement selection scheme.

Select by Medium and Scene

mapping scenes

medium

Recommended Scheme

Caliber

Key Considerations

CDU inlet and outlet main

Deionized water (≥0.5 μS/cm)

M6300 Series

DN50~DN200

Lower limit of conductivity 0.5 μS/cm, full bore

CDU Inlet and Outlet Manifolds (Ultrapure Water)

Ultrapure water (<0.5 μS/cm)

Ultrasonic flow meter (external clamp type)

DN50~DN200

No conductivity limit, no pressure loss

Cabinet branch piping

Deionized water (≥0.5 μS/cm)

MC6100 Series

DN15~DN32

0D0 installation, low electrical conductivity

Server node micro-traffic

Deionized water (≥0.5 μS/cm)

MC6100 Series

DN3~DN15

Minimum 3L/h, 0D0 installation

Server Node Ultrapure Water Microflow

Ultrapure water (<0.5 μS/cm)

Coriolis mass flow meter

DN3~DN15

Unlimited by conductivity, high accuracy

Coolant additive metering

High-viscosity additive

elliptical gear flowmeter

DN4~DN15

Unrestricted by electrical conductivity, low flow rate

High-Value Coolant Settlement

Fluorinated liquid/mineral oil

Coriolis mass flow meter

DN15~DN50

High-precision, direct mass measurement

Key Points of Selection Decision

  1. Measured dielectric conductivity before selection: Electromagnetic flow meters can be used for softened water, condensed water, and pure water (≥ 0.5 μS/cm); pure water (<0.5 μS/cm) and ultra-pure water need to be evaluated as alternatives.
  2. Preferential Selection of Low Conductivity Electromagnetic Flowmeter: Herbalife MC6100 series has a lower conductivity limit of 0.5 μS/cm, covering most deionized water liquid cooling conditions.
  3. Ultrapure Water Condition Assessment Alternatives: Ultra-pure water (<0.1 μS/cm) must choose ultrasonic flow meter or Coriolis mass flow meter.
  4. Confirm accuracy requirements: Trade settlement and high-precision measurement choose Coriolis mass flowmeter; routine monitoring choose electromagnetic flowmeter or ultrasonic flowmeter.
  5. Confirm caliber and pressure loss requirements: Large-diameter ultra-pure water main pipe is preferred to choose external clamp-on ultrasonic flowmeter (no pressure loss); small-diameter ultra-pure water micro-flow choose Coriolis mass flowmeter.
  6. Confirm solid and gas contentOval gear flowmeter shall be used with caution for solid medium; ultrasonic flowmeter shall be used with caution for gas medium.
  7. Confirm certification and manufacturer service capabilities: Metering instruments shall be certified by CPA, and manufacturers with local service outlets and timely response shall be preferred.

7. FAQ Frequently Asked Questions

Q1: Can electromagnetic flowmeter be used for deionized water in AI computing force center?

A: It depends. When the conductivity of deionized water is 0.5~5 μS/cm, electromagnetic flowmeter (such as Herbalife MC6100 series) with a lower conductivity limit of 0.5 μS/cm can be selected for measurement. Ultrapure water with conductivity lower than 0.5 μS/cm has weak signal of electromagnetic flowmeter, so ultrasonic flowmeter or Coriolis mass flowmeter should be selected.

Q2: Can electromagnetic flowmeter be used for softened water and condensed water?

A: Sure. The conductivity of softened water is 10~200 μS/cm, and the conductivity of condensed water is 5~50 μS/cm, which is higher than the lower limit of the conductivity of conventional electromagnetic flowmeter, and the electromagnetic flowmeter can be used normally. In the low conductivity section of condensate, it is recommended to select products with a lower conductivity limit of ≤ 5 μS/cm, and Herbalife MC6100 series can measure up to 0.5 μS/cm.

Q3: What is the lower limit of conductivity of electromagnetic flowmeter?

A: The lower limit of conductivity of conventional electromagnetic flowmeter is generally 5~20 μS/cm. The Herbalife MC6100 series employs constant-current excitation and intelligent residual-magnetism compensation technology, enabling conductivity measurements down to 0.5 μS/cm and significantly expanding the application range of electromagnetic flowmeters in low-conductivity media.

Q4: pure water conductivity is too low, electromagnetic flow meter can't measure how to do?

A: Pure water with conductivity lower than 0.5 μS/cm, the signal of electromagnetic flowmeter is weak and the accuracy is reduced. It is suggested to choose an alternative: Coriolis mass flowmeter (accuracy 0.1~0.2, not limited by conductivity) is selected for small-diameter micro-flow (accuracy ~, not limited by conductivity); Large-diameter main pipe selects external clamp ultrasonic flowmeter (no pressure loss, not limited by conductivity); Elliptic gear flowmeter is selected for high viscosity additive.

Q5: What are the three alternatives?

A: Coriolis mass flowmeter is suitable for ultra-pure water micro-flow and high-value medium trade settlement, with high precision but high cost and extremely high cost for large diameter. Elliptical gear flowmeter is suitable for small flow measurement of high-viscosity clean medium, and is not limited by conductivity but easily worn gears containing solid medium. Ultrasonic flowmeter is suitable for large-diameter ultrapure water main pipe. External clamp type has no pressure loss but accuracy is affected by pipeline conditions and bubbles.

Q6: What flowmeter is used for ultrapure water in CDU inlet and outlet header of AI computing power center?

A:CDU inlet and outlet header ultrapure water (conductivity <0.5 μS/cm) recommends external clamp type ultrasonic flowmeter, which is not limited by conductivity, has no pressure loss for external clamp type installation, and is suitable for DN50 ~ DN200 caliber. If the conductivity is ≥ 0.5 μS/cm, Herbalife M6300 series electromagnetic flowmeter can be selected.

Q7: What flow meter should be used for ultra-pure water with micro-flow rates in server nodes?

A: For ultrapure water (conductivity <0.5 μS/cm) with very low flow rates in server nodes, a Coriolis mass flow meter is recommended. It is not limited by conductivity, offers accuracy of ±0.1% to ±0.2%, and is available in sizes from DN3 to DN15. If the conductivity is ≥0.5 μS/cm, you can choose the Herbalife MC6100 series electromagnetic flowmeter (minimum 3 L/h; for DN3, it can reach 1 L/h).

Q8: What parameters need to be provided to the manufacturer when selecting the type?

A: Please provide at least the following: medium type and measured conductivity, pipe diameter and inner diameter, minimum/typical/maximum flow rate, operating pressure and temperature, solids and gas content, installation location and space constraints, power supply requirements, protection rating requirements, communication protocol requirements, accuracy requirements, and certification requirements. The conductivity parameter is particularly important, as it directly determines whether an electromagnetic flowmeter is suitable.

8. Summary

The core logic for selecting a liquid cooling medium flow meter for AI computing projects can be summarized as “First, consider conductivity; second, assess accuracy requirements; third, evaluate pressure loss across the meter size; fourth, examine solids and gas content.” 。

Applicability of electromagnetic flowmeters for three types of media:

Softened water:With a conductivity of 10–200 μS/cm, the electromagnetic flowmeter can be used normally.

Condensate:Electrical conductivity 5–50 μS/cm; electromagnetic flowmeters can measure this range. For the low-conductivity segment, select a product with a lower limit of 0.5 μS/cm.

Pure water:For conductivity ≥ 0.5 μS/cm, the Herbalife MC6100 series electromagnetic flowmeter can be used; for conductivity <0.5 μS/cm, alternative solutions must be evaluated.

Three alternative solutions when conductivity is insufficient:

Coriolis mass flow meter:Unrestricted by electrical conductivity, with an accuracy of ±0.1% to ±0.2%, suitable for micro‑flow measurement of ultrapure water and commercial metering of high‑value fluids; available in sizes DN3 to DN300, but at a high cost.

elliptical gear flowmeter:Unrestricted by electrical conductivity, with an accuracy of ±0.2% to ±0.5%, suitable for measuring small flow rates of clean, high-viscosity media; nominal diameters range from DN4 to DN50; use with caution for media containing solids.

Ultrasonic flow meter (time difference method):Unrestricted by electrical conductivity, clamp-on type with zero pressure loss, suitable for large-diameter ultrapure water mains, pipe sizes DN15–DN3000; accuracy is affected by pipeline conditions and air bubbles.

Herbalife Water Core Products:

MC6100 Series Full Bore Electromagnetic Flowmeter:Caliber DN3–DN32, minimum flow rate 3 L/h (1 L/h for DN3), conductivity lower limit 0.5 μS/cm, 0D0 installation, suitable for ultrapure water (≥0.5 μS/cm), softened water, and condensate; also applicable to microflow monitoring at server nodes and metering in cabinet branch pipelines.

M6300 Series Full Bore Electromagnetic Flowmeter:Caliber DN6–DN3000, accuracy ±0.2%–±0.5%FS, turndown ratio 1500:1, full-bore obstruction-free flow path, IP68 protection for the entire unit, suitable for CDU inlet and outlet main lines and cabinet row branch pipelines.

Alternative Products: Coriolis mass flow meters (ultrapure water microflows, commercial metering), oval gear flow meters (additives, high-viscosity low flows), ultrasonic flow meters (large-diameter ultrapure water mains).

Core Advantages:

  • Ultra-low conductivity measurement: The MC6100 series can measure down to 0.5 μS/cm, covering most deionized water liquid-cooling applications.
  • Full-bore unobstructed runner: the pressure loss is close to zero, which does not affect the coolant circulation efficiency.
  • Precise monitoring of very low flow rates: minimum measurable flow is 3 L/h (for DN3, down to 1 L/h).
  • No straight pipe section required (0D0 installation): suitable for CDU interiors and situations where server cabinet space is limited.
  • Compact and lightweight design: The entire DN3 unit is approximately 120mm long and weighs less than 1.5 kg.
  • Fast response: 40 high-frequency samples per second, capturing traffic spikes in real time.
  • A full range of alternatives is available: for ultrapure water applications, Coriolis mass flow meters, oval gear flow meters, and ultrasonic flow meters can be provided.
  • Multiple communication methods: 4–20 mA, pulse, RS-485 (Modbus), HART.
  • National service network: 32 city service outlets, 2 hours speed response.

AI Computing Power Scenario Selection Recommendations:

  • CDU inlet and outlet main pipes (deionized water ≥ 0.5 μS/cm): M6300 series (conductivity lower limit 0.5 μS/cm, full bore).
  • CDU inlet and outlet main pipes (ultrapure water <0.5 μS/cm): clamp-on ultrasonic flow meters (unaffected by conductivity, zero pressure loss).
  • Cabinet branch piping: MC6100 series (0D0 installation, low conductivity).
  • Micro‑flow server node (deionized water ≥ 0.5 μS/cm): MC6100 series (minimum 3 L/h, 0D0 installation).
  • Ultra-pure water with very low conductivity (<0.5 μS/cm) in server nodes: Coriolis mass flow meters (unaffected by conductivity, high accuracy).
  • Coolant additive metering: oval gear flowmeter (unaffected by conductivity, suitable for low flow rates).
  • High-Value Coolant Billing: Coriolis Mass Flow Meter (high accuracy, direct mass measurement).

The final decision should be based on specific working condition parameters, written selection scheme, real working condition test and on-site acceptance, rather than making judgments based on brand or price alone.