Product Features
1.0.5% linearity, 0.2% repeatability;
2. Non-conductive/special medium measurement;
3. Low voltage multi-pulse balanced transmitting and receiving;
4. Positive/negative/net accumulator;
5. Isolated RS-485 interface, support MODBUS RTU;
6. Anti-interference design, electrically isolated DC power supply;
7. Built-in heat measurement/calorimeter;
8.2-way two-wire PT1000 platinum resistance input circuit;
9.1 analog 4-20mA output, OCT frequency signal output;
10. Optional DC/AC/220 AC power supply;
11, the number of sampling times per cycle increased to 128, 22 picosecond time difference measurement resolution;
How to use
(1) Introduction to the window
The main groups of the window are: flow display, sensor settings, communication settings, output settings, clear flow, 4 ~ 20mA calibration, etc. The subgroups are described below:
1. Flow display: used to display the window, showing instantaneous flow, positive cumulative flow, negative cumulative flow, net cumulative flow, instantaneous flow rate, date and time, current output, etc.
2. Sensor settings: set the sensor type, pipe diameter, pipe wall thickness, fluid type, probe type, probe installation method and other parameters, display the installation distance.
3. Communication settings: Set RS485 communication baud rate, modbus RTU communication address, etc.
4. Output settings: used to set the instantaneous flow corresponding to 4 ~ 20mA, OCT pulse output correlation
5. Clear flow: used to clear cumulative flow, historical flow records, etc. Clear cumulative flow meter requires a password. Please contact the manufacturer for the password.
6.4 ~ 20mA Calibration: Used to calibrate 4 ~ 20mA output calibration.
(2) Quickly input pipeline parameters and steps:
1. M50, sensor type (the host supports a variety of probes), sensors mainly include plug-in type, surface-mounted type or specific sensors whose parameters have been written into the equipment; If the sensor is an integrated pipe section of pipe section and the parameters are not written into the equipment, such as DN100 and DN200, the sensor type is plug-in type; Except for the integrated pipe section with special parameters written.
2. M56管道内径
3. M57 pipe wall thickness: M50 is selected as surface-mounted type with this item
4. M58 pipe material: M50 is selected as surface-mounted type with this item
5. M64 fluid type: water by default
6. Installation method of M51 probe: Z, V, N, W,M50 is selected as surface mount type
7. M137固化参数(此操作非常重要)
8. M9501设置为传感器设置
9.M518显示Q(信号质量),T(时间传输比);一般情况下要求Q(信号质量)大于50%,时间传输比T在100±3%以内;M543查看信号质量,要求信号质量大于40%
10. M514显示第一声道的瞬时流量。
11. M9501设置为流量显示界面
如果设备为双声道流量计,则还需要查看第二声道传感器数据,查询与设置方法与第10、11步相同,但是窗口则变为M618、M614、M543。
(3)、判断流量计工作是否正常
> M518: 如果Q>80 97%
> M618: 如果Q>80 97%
注意事项
1、观察安装现场管道是否满足直管段前10D后5D以及离泵30D的距离。(D为管道内直径)
2、确认管道内流体介质以及是否满管。
3、确认管道材质以及壁厚(充分考虑到管道内壁结垢厚度)
4、确认管道使用年限,在使用10左右的管道,即使是碳钢材质,建议也采用插入式安装。
5、前四步骤完成后可确认使用何种传感器安装
6、开始向表体输入参数以确定安装距离。
7、非常重要:精确测量出安装距离。
Technical Specifications
项目性能,参数
测 量 主 机精 度1.0 %
重 复 性0.2%
流速范围0.1 ~ ±7 m/s。
测量原理超声波传播时差原理,32位CPU工作,8字节双浮点运算。
测量周期50mS. (每秒20次,每个周期采集64组数据)。
显 示2×10或者4*8背光型汉字液晶显示器,低功耗为段码液晶显示。
操 作4×4轻触键盘/4按键输入。
输 入2路二线制PT1000铂电阻输入回路,可实现热量计量功能
输 出电流信号:4~20mA, 阻抗0~500W,浮空,精度0.1%FS。脉冲信号:正、负、净流量及热量累计脉冲OCT输出。数据接口:标准隔离RS-485接口。
其他功能记忆日、月、年累积流量。故障自诊断功能;网络工作方式等。
传 感 器中型标准M1型,适用于管径DN50~DN700mm
插入式:测量管道材质不限(可焊接、不可焊接都可以)适用于管径DN80以上。
标准管段式:适用于管径DN10-DN400,整机测量精度±0.5%。
电缆长度可加长至100m(超过此长度请同厂家联系)。
管道衬 材钢、不锈钢、铸铁、硬质塑料、水泥管等一切质地密致管道,允许有衬里。
内 径50mm -300mm。
直管段长度上游≥10D,下游≥5D,距泵出口处≥30D。
流 体种 类水、海水、酸碱液、食物油、汽、煤、柴油、原油、酒精、啤酒等能传播超声波的均匀液体。
浊 度≤10000 ppm, 且气泡含量小。
温 度-10~150℃。
流 向可对正反向流量分别计量,并可计量净流量。
工作环境温 度主机:-10-70℃ (大于此温度范围要求请与厂家联系)探头:-30℃ ~ +150℃
湿 度主机:85%RH探头:可浸水工作,水深≤3米。
电 源JHA型普通版:DC24V ,AC220V供电方式。JHA型低功耗版:3.6v锂电池/5~9V (或者9~36V)。